Technical data, mains supply 1 x 220 -
240 V/3 x 200-240V
According to . international
standards
Type
2803
2805
2807
2811
2815
2822
2840
Output current
I
INV.
[A]
2.2
3.2
4.2
6.0
6.8
9.6
16
(3 x 200-240V)
I
MAX
(60s) [A]
3.5
5.1
6.7
9.6
10.8
15.3
25.6
Output power (230 V)
S
INV.
[KVA]
0.9
1.3
1.7
2.4
2.7
3.8
6.4
Typical shaft output
P
M,N
[kW]
0.37
0.55
0.75
1.1
1.5
2.2
3.7
Typical shaft output
P
M,N
[HP]
0.5
0.75
1.0
1.5
2.0
3.0
5.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Input current
I
L,N
[A]
5.9
8.3
10.6
14.5
15.2
-
-
(1 x 220-240 V)
I
L,MAX
(60s) [A]
9.4
13.3
16.7
23.2
24.3
-
-
Input current
I
L,N
[A]
2.9
4.0
5.1
7.0
7.6
8.8
14.7
(3 x 200-240 V)
I
L,MAX
(60s) [A]
4.6
6.4
8.2
11.2
12.2
14.1
23.5
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
IEC/UL
2)
[A]
20/20
20/20
20/20
20/20
20/20
20/20
25/25
Efficiency
3)
[%]
95
95
95
95
95
95
95
Power loss at 100%
load
[W]
24
35
48
69
94
125
231
Weight
[kg]
2.0
2.0
2.0
2.0
2.0
3,7
6.0
Enclosure
4
type
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
1. American Wire Gauge. Max. cable cross
section is the largest cable cross section that can
be attached to the terminals. Always observe
national and local regulations.
2. Type gG pre-fuses must be used for installation
according to IEC rules. If you want to maintain
UL/cUL you must use pre-fuses of the type
Bussmann KTN-R 200 V, KTS-R 500 V or Ferraz
Shawmut, type ATMR (max. 30A). The fuses
must be placed for protection in a circuit that is
capable of supplying a maximum of 100,000 amps
RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured
motor cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875,
whereas NEMA 1 is an option.
MG.28.E9.02 - VLT is a registered Danfoss trademark
150