VLT
®
2800 Series
■
Motor coils
By fitting the motor coil module between the frequency
converter and the motor it is possible to use up
to 200 metres of unscreened/unarmoured motor
cable or 100 metres of screened/armoured motor
cable. The motor coil module has an enclosure of
IP 20 and can be installed side-by-side.
NB!:
To have long motor cables and still comply
with EN55011-1A, motor coil and
EMC filter
for long motor cables
are needed.
NB!:
To comply with EN55011-1A
the EMC filter for
long motor cables
can only be fitted to a VLT
2800 with integral 1A filter (R1 option).
See also the section EMC Emission.
Technical data for VLT 2803-2875 Motor coils
Max. cable length (unscreened/unarmoured)
1)
200 m
Max. cable length (screened/armoured)
1)
100 m
Enclosure
IP 20
Max. rated current
1)
16 A
Max. voltage
1)
480 V AC
Min. distance between VLT and motor coil
Side-by-side
Min. distance above and below motor coil
100 mm
Dimensions H x W x D (mm)
2)
200 x 90 x 152
Weight
3.8 kg
1)
Parameter 411
Switching frequency
= 4500 Hz.
2)
For mechanical dimensions see under
Mechanical dimensions
.
See ordering number for motor coil module
under
Accessories for VLT 2800
.
MG.28.E9.02 - VLT is a registered Danfoss trademark