4 Device Configuration
4.1 Before Configuring the Device
N O T I C E
The error LED flashes whenever the device is receiving power but is not connected to a network. The error LED will flash occa-
sionally during the configuration process.
N O T I C E
At power-up, the communication card loads the IP address stored in the soft starter.
4.2 Configuration Methods
Network communication parameters for the communication card can be set via the soft starter or via the on-board web server.
The card uses a static IP address by default. To enable DHCP addressing, set
parameter 12–20 DHCP
to enable or change the
setting via the on-board web server.
The IP address can be set via the programmable parameters of the soft starter.
The web server can configure the IP address and messaging settings for MQTT/OPC UA operation.
4.3 Parameters for Configuring Network Settings
Use
parameters 12-8
to
12-21
to configure the network address. The parameters can be set via the Main Menu, via the Setup Tools,
or by uploading a configuration file via USB Save & Load.
Parameter
Default
12-8 Gateway Address
192
12-9 Gateway Address 2
168
12-10 Gateway Address 3
0
12-11 Gateway Address 4
100
12-12 IP Address
192
12-13 IP Address 2
168
12-14 IP Address 3
0
12-15 IP Address 4
2
12-16 Subnet Mask
255
12-17 Subnet Mask 2
255
12-18 Subnet Mask 3
255
12-19 Subnet Mask 4
0
12-20 DHCP
Disable
12-21 Location ID
0
4.4 Enabling Network Control
N O T I C E
If the reset input is active, the soft starter does not operate. If a reset switch is not required, use
parameter 7-9
to set the reset
input to normally open or fit a link across terminals RESET, COM+ on the soft starter.
AN353423548483en-000101 / 130R0945 | 9
Danfoss A/S © 2020.12
Device Configuration
EtherNet/IP Card
Installation Guide