1
Primary Mtr Set
5-4
Auto-Stop Time
8
Display
8-1
Language
8-2
User Scrn Top L
8-3
User Scrn Top R
8-4
User Scrn Btm L
8-5
User Scrn Btm R
Table 7.1 Parameters in the Quick Set-up Menu
7.2.2 Application Set-up Examples
The application set-ups menu makes it easy to configure
the soft starter for common applications. The soft starter
selects the parameters relevant to the application and
suggests a typical setting. Each parameter can be adjusted
to suit the exact requirements.
On the display, the highlighted values are suggested
values. The values indicated by
▶
are the loaded values.
Always set
parameter 1-1 Motor FLC
to match the motor
nameplate full load current. The suggested value for motor
FLC is the minimum FLC of the soft starter.
Centrifugal pump
Motor Full Load Current
Start mode
Adaptive control
Adaptive start profile
Early acceleration
Start ramp time
10 s
Stop mode
Adaptive control
Adaptive stop profile
Late deceleration
Stop time
15 s
Table 7.2 Suggested Values for Centrifugal Pump Applications
Submersible pump
Motor Full Load Current
Start mode
Adaptive control
Adaptive start profile
Early acceleration
Start ramp time
5 s
Stop mode
Adaptive control
Adaptive stop profile
Late deceleration
Stop time
5 s
Table 7.3 Suggested Values for Submersible Pump Applications
Damped fan
Motor Full Load Current
Start mode
Constant current
Current limit
350%
Table 7.4 Suggested Values for Damped Fan Applications
Undamped fan
Motor Full Load Current
Start mode
Adaptive control
Adaptive start profile
Constant acceleration
Start ramp time
20 s
Excess start time
30 s
Locked rotor time
20 s
Table 7.5 Suggested Values for Undamped Fan Applications
Compressor screw
Motor Full Load Current
Start mode
Constant current
Start ramp time
5 s
Current limit
400%
Table 7.6 Suggested Values for Compressor Screw Applications
Compressor recip
Motor Full Load Current
Start mode
Constant current
Start ramp time
10 s
Current limit
450%
Table 7.7 Suggested Values for Compressor Recip Applications
Conveyor
Motor Full Load Current
Start mode
Constant current
Start ramp time
5 s
Current limit
400%
Stop mode
Adaptive control
Adaptive stop profile
Constant deceleration
Stop time
10 s
Table 7.8 Suggested Values for Conveyor Applications
Crusher rotary
Motor Full Load Current
Start mode
Constant current
Start ramp time
10 s
Current limit
400%
Excess start time
30 s
Locked rotor time
20 s
Table 7.9 Suggested Values for Crusher Rotary Applications
Programming
Operating Guide
MG17K602