8-52 DC Brake Select
Option:
Function:
[3] Logic OR
Activates start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates a start command via a digital input.
[1]
Bus
Activates a start command via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates a start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates a start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:
Function:
[0]
Digital
input
Select control of the frequency converter
reverse function via the terminals (digital input)
and/or via the fieldbus.
[1]
Bus
Activates the reverse command via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates the reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the reverse command via the
fieldbus/serial communication port OR via one
of the digital inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
input
Activates preset reference selection via a digital
input.
[1]
Bus
Activates preset reference selection via the
serial communication port or fieldbus option.
[2]
Logic
AND
Activates preset reference selection via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
fieldbus/serial communication port OR via one
of the digital inputs.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
6.2 9-** and 16-** PROFIBUS Parameters
9-15 PCD Write Configuration
Array [10]
Option:
Function:
Select the parameters
to be assigned to PCD
3 to 10 of the
telegrams. The number
of available PCDs
depends on the
telegram type. The
values in PCD 3 to 10
are then written to the
selected parameters as
data values. Alterna-
tively, specify a
standard PROFIBUS
telegram in
9-22 Telegram
Selection
.
[0]
None
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp Up Time
Parameters
Programming Guide
MG37G102