
Parameters
130BE208.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
≈ 5kΩ
FC
+24 V
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50
Parameter 6-19 T
erminal 53 mode
[1] Voltage
* = Default value
Notes/comments:
Table 7.4 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
130BF100.10
+24 V
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
*[8] Start
Parameter 5-12 T
erminal 27
Digital Input
[19] Freeze
Reference
Parameter 5-13 T
erminal 29
Digital Input
[21] Speed Up
Parameter 5-14 T
erminal 32
Digital Input
[22] Speed
Down
* = Default value
Notes/comments:
Table 7.5 Speed Up/Speed Down
130BB840.12
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 7.1 Speed Up/Speed Down
7.2.3 Start/Stop
Parameters
130BF098.10
FC
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
19
18
27
29
32
33
50
53
54
55
42
+24 V
13
Function
Setting
Parameter 5-10 Ter
minal 18 Digital
Input
[8] Start
Parameter 5-11 Ter
minal 19 Digital
Input
*[10]
Reversing
Parameter 5-12 Ter
minal 27 Digital
Input
[0] No
operation
Parameter 5-14 Ter
minal 32 Digital
Input
[16] Preset
ref bit 0
Parameter 5-15 Ter
minal 33 Digital
Input
[17] Preset
ref bit 1
Parameter 3-10 Pre
set Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
* = Default value
Notes/comments:
Table 7.6 Start/Stop with Reversing and 4 Preset Speeds
Application Examples
Operating Guide
MG07A402
Danfoss A/S © 10/2017 All rights reserved.
43
7
7