Table 156: 8-10 - Main Contactor Time
Range
Function
*400 ms 100–2000
ms
Sets the delay period between the soft starter switching the main contactor output (terminals 13, 14) and
beginning the pre-start checks (before a start), or entering the not-ready state (after a stop). Set accord-
ing to the specifications of the main contactor used.
10.13 Parameter Group 9-** Analog Output
Table 157: 9-1 - Analog Output A
Option
Function
Selects the information reported via the analog output.
* Current (% FLC)
Current as a percentage of motor full load current.
Motor Temp (%)
The motor's temperature, calculated by the thermal model.
Motor pf
Motor power factor, measured by the soft starter.
Motor Power (%kW)
Motor power, as a percentage of the programmed power.
Heat Sink Temperature
(%)
The soft starter temperature as a percentage of the maximum allowed operating temperature
of the heat sink.
Table 158: 9-2 - Analog A Scale
Range
Function
Selects the range of the analog output.
0–20 mA
*
4–20 mA
Table 159: 9-3 - Analog A Maximum Adjustment
Range
Function
* 100% 0–600% Calibrates the upper limit of the analog output to match the signal measured on an external current measur-
ing device.
Table 160: 9-4 - Analog A Minimum Adjustment
Range
Function
* 0% 0–600% Calibrates the lower limit of the analog output to match the signal measured on an external current measuring
device.
10.14 Parameter Group 10-** Display
Table 161: 10-1 - Language
Option
Function
Selects in which language the LCP shows messages and feedback.
*
English
Chinese
Español
Deutsch