1 Introduction

1.1 Description

This Installation Guide explains how to install the LCP for VLT® HVAC Basic Drive FC 101 and VLT® Flow Drive FC 111.

1.2 Item Supplied

VLT® Control Panel LCP 32 (ordering number: 132B9221).
VLT® Control Panel LCP 31 (ordering number: 132B0200).

1.3 Safety Precautions

Only qualified personnel are allowed to install the LCP described in this Installation Guide.
For important information about safety precautions for installation, refer to the drive's Operating Guide.

W A R N I N G

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or
serious injury.

Stop the motor.
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table 

Discharge time

 and is also visible

on the nameplate on top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.

Table 1: Discharge Time for FC 101

Voltage [V]

Power range [kW (hp)]

Minimum waiting time (minutes)

3x200

0.25–3.7 (0.33–5)

4

3x200

5.5–11 (7–15)

15

3x400

0.37–7.5 (0.5–10)

4

3x400

11–90 (15–125)

15

3x600

2.2–7.5 (3–10)

4

3x600

11–90 (15–125)

15

Table 2: Discharge Time for FC 111

Voltage [V]

Power range [kW (hp)]

Minimum waiting time (minutes)

3x400

0.37–7.5 (0.5–10)

4

3x400

11–90 (15–125)

15

3x400

110–315 (150–450)

20

AN359636476228en-000201 / 130R0961 | 1

Danfoss A/S © 2021.03

Installation Guide

VLT® Control Panel LCP