5-41 On Delay, Relay
Array [8](Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s*
[0.01 - 600.00 s]
Enter the delay of the relay cut-in time. Select one of available mechanical relays and MCO 105 in
an array function. See par.5-40
. Relay 3-6 are included in MCB 112 (ATEX).
5-42 Off Delay, Relay
Array [8] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s*
[0.01 - 600.00 s]
Enter the delay of the relay cut-out time. Select one of available mechanical relays and MCO 105 in
an array function. See par.5-40
.
If the selected event condition changes before the on or off delay timer expires, the relay output is unaffected.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-74