22-20 Low Power Auto Set-up
Option:
Function:
When set for
Enabled
, an auto set-up sequence is activated, automatically setting speed to approx.
50% and 85% of rated motor speed (par.4-13
). At those two speeds, the power consumption is automatically measured and stored.
Before enabling Auto Set-up:
1.
Close valve(s) in order to create a no-flow condition
2.
The adjustable frequency drive must be set for open-loop (par.1-00
Note that it is important also to set par.1-03
[0] *
OFF
[1]
Enabled
NOTE!
Auto set-up must be done when the system has reached normal operating temperature!
NOTE!
It is important that the par.4-13
is set to the max. operational
speed of the motor!
It is important to do the auto set-up before configuring the integrated PI controller as settings will be reset when changing from closed
to open-loop in par.1-00
.
NOTE!
Carry out the tuning with the same settings in par.1-03
, as for operation after the tuning.
22-21 Low Power Detection
Option:
Function:
[0] *
Disabled
[1]
Enabled
If selecting Enabled, the low power detection commissioning must be carried out in order to set the
parameters in group 22-3* for proper operation!
22-22 Low Speed Detection
Option:
Function:
[0] *
Disabled
[1]
Enabled
Select Enabled for detecting when the motor operates with a speed as set in par.4-11
.