
15-12 Trigger Event
Option:
Function:
Selects the trigger event. When the trigger event occurs, a window is applied to freeze the log. The
log will then retain a specified percentage of samples before the occurrence of the trigger event
(par.15-14
).
[0] *
FALSE
[1]
TRUE
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reverse
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-146
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3