[70]
SL Timeout 3
[71]
SL Timeout 4
[72]
SL Timeout 5
[73]
SL Timeout 6
[74]
SL Timeout 7
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-52 SL Controller Action
Array [20]
Option:
Function:
Select the action corresponding to the SLC event. Actions are executed when the corresponding
event (defined in par.13-51
) is evaluated as true. The following actions are
available for selection:
[0] *
DISABLED
[1]
No action
[2]
Select set-up 1
Changes the active set-up (par.0-10
) to ‘1’.
[3]
Select set-up 2
Changes the active set-up (par.0-10
) to ‘2’.
[4]
Select set-up 3
Changes the active set-up (par.0-10
) to ‘3’.
[5]
Select set-up 4
Changes the active set-up (par.0-10
) to ‘4’. If the set-up is changed, it will merge with
other set-up commands coming from either the digital inputs or via a serial communication bus.
[10]
Select preset ref 0
Selects preset reference 0.
[11]
Select preset ref 1
Selects preset reference 1.
[12]
Select preset ref 2
Selects preset reference 2.
[13]
Select preset ref 3
Selects preset reference 3.
[14]
Select preset ref 4
Selects preset reference 4.
[15]
Select preset ref 5
Selects preset reference 5.
[16]
Select preset ref 6
Selects preset reference 6.
[17]
Select preset ref 7
Selects preset reference 7. If the active preset reference is changed, it will merge with other preset
reference commands coming from either the digital inputs or via a serial communication bus.
[18]
Select ramp 1
Selects ramp 1
[19]
Select ramp 2
Selects ramp 2
[22]
Run
Issues a start command to the adjustable frequency drive.
[23]
Run reverse
Issues a start reverse command to the adjustable frequency drive.
[24]
Stop
Issues a stop command to the adjustable frequency drive.
[26]
Dcstop
[27]
Coast
The adjustable frequency drive coasts immediately. All stop commands including the coast com-
mand stop the SLC.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-132
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3