3.13.2 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option:
Function:
[0] *
Off
Disables the Smart Logic Controller.
[1]
On
Enables the Smart Logic Controller.
13-01 Start Event
Option:
Function:
Select the Boolean (TRUE or FALSE) input to activate Smart Logic Control.
[0] *
FALSE
Enters the fixed value of FALSE in the logic rule.
[1]
TRUE
Enters the fixed value TRUE in the logic rule.
[2]
Running
See parameter group 5-3* for further description.
[3]
In range
See parameter group 5-3* for further description.
[4]
On reference
See parameter group 5-3* for further description.
[5]
Torque limit
See parameter group 5-3* for further description.
[6]
Current limit
See parameter group 5-3* for further description.
[7]
Out of current range
See parameter group 5-3* for further description.
[8]
Below I low
See parameter group 5-3* for further description.
[9]
Above I high
See parameter group 5-3* for further description.
[10]
Out of speed range
[11]
Below speed low
See parameter group 5-3* for further description.
[12]
Above speed high
See parameter group 5-3* for further description.
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
See parameter group 5-3* for further description.
[17]
Mains out of range
See parameter group 5-3* for further description.
[18]
Reverse
See parameter group 5-3* for further description.
[19]
Warning
See parameter group 5-3* for further description.
[20]
Alarm (trip)
See parameter group 5-3* for further description.
[21]
Alarm (trip lock)
See parameter group 5-3* for further description.
[22]
Comparator 0
Use the result of comparator 0 in the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic rule.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-119