8-40 Telegram selection
Option:
Function:
Enables use of freely configurable messages or standard messages for the adjustable frequency
drive port.
[1] *
Standard telegram 1
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
[108]
PPO 8
[200]
Custom telegram 1
3.9.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0]
Digital input
[1]
Bus
Activates Start command via the serial communication port or serial communication option.
[2]
Logic AND
Activates Start command via the serial communication bus/serial communication port, AND addi-
tionally via one of the digital inputs.
[3] *
Logic OR
Activates Start command via the serial communication bus/serial communication port OR via one of
the digital inputs.
NOTE!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals (digital input) and/or via the serial communication
bus.
[0]
Digital input
[1]
Bus
Activates Start command via the serial communication port or serial communication option.
[2]
Logic AND
Activates Start command via the serial communication bus/serial communication port, AND addi-
tionally via one of the digital inputs.
[3] *
Logic OR
Activates Start command via the serial communication bus/serial communication port OR via one of
the digital inputs.