5.3 Connection Examples for Control of
Motor with External Signal Provider
NOTICE
The following examples refer only to the drive system’s
control card,
not
the filter.
5.3.1 Start/Stop
Terminal 18 =
Parameter 5-10 Terminal 18 Digital Input
[8]
Start
.
Terminal 27 =
Parameter 5-12 Terminal 27 Digital Input
[0]
No operation
(Default
coast inverse
)
Terminal 37 = Safe Torque Off.
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 5.5 Start/Stop Parameters
5.3.2 Pulse Start/Stop
Terminal 18 =
Parameter 5-10 Terminal 18 Digital Input
[9]
Latched start
.
Terminal 27=
Parameter 5-12 Terminal 27 Digital Input
[6]
Stop inverse
.
Terminal 37 = Safe Torque Off.
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
Illustration 5.6 Pulse Start/Stop Parameters
5.3.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 =
Parameter 5-10 Terminal 18 Digital
Input
[9] Start
(default).
Terminal 27 =
Parameter 5-12 Terminal 27 Digital
Input
[19] Freeze reference
.
Terminal 29 =
Parameter 5-13 Terminal 29 Digital
Input
[21] Speed up
.
Terminal 32 =
Parameter 5-14 Terminal 32 Digital
Input
[22] Speed down
.
12
18
27
29
32
37
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
130BA021.12
Illustration 5.7 Speed Control Parameters
Application Set-up Examples
User Guide
MG37L202