8-53 Start Select
Option:
Function:
[1]
Bus
Activates a start command via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates a start command via the fieldbus/serial
communication port, AND additionally via 1 of
the digital inputs.
[3]
*
Logic OR
Activates a start command via the fieldbus/serial
communication port, OR via 1 of the digital
inputs.
8-54 Reversing Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
Select control of the frequency converter reverse
function via the terminals (digital input) and/or via
the fieldbus.
[0] Digital
input
Activates reverse command via a digital input.
[1] Bus
Activates reverse command via the serial
communication port or fieldbus option.
[2] Logic
AND
Activates reverse command via the fieldbus/serial
communication port, AND via 1 of the digital
inputs.
[3] Logic OR Activates reverse command via the fieldbus/serial
communication port OR via 1 of the digital inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port, or fieldbus option.
[2]
Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, AND via 1 of the
digital inputs.
[3]
*
Logic OR
Activates the set-up selection via the fieldbus/
serial communication port OR via 1 of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
8-56 Preset Reference Select
Option:
Function:
[0]
Digital
input
Activates preset reference selection via a digital
input.
[1]
Bus
Activates preset reference selection via the
serial communication port, or fieldbus option.
[2]
Logic AND Activates preset reference selection via the
fieldbus/serial communication port, AND via 1
of the digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
fieldbus/serial communication port, OR via 1 of
the digital inputs.
3.9.6 8-7* BACnet
NOTICE
Parameters in this group are active only when
is set to
[5] BACnet
.
8-70 BACnet Device Instance
Range:
Function:
1
*
[0 - 4194302 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range:
Function:
127
*
[1 - 127 ] Define the address of the master which holds
the highest address in this network. Decreasing
this value optimises polling for the token.
8-73 MS/TP Max Info Frames
Range:
Function:
1
*
[1 - 65534 ] Define how many info/data frames the device
is allowed to send while holding the token.
8-74 "I-Am" Service
Option:
Function:
[0]
*
Send at power-
up
[1]
Continuously
Select whether the device should send the
"I-Am" service message only at power-up,
or continuously with an interval of approx-
imately 1 min.
8-75 Initialisation Password
Range:
Function:
Size related
*
[1 - 20 ]