[65] Reset
Counter B
Input for reset of counter B.
[66] Sleep Mode
Forces frequency converter into Sleep mode
(see parameter group 22-4*). Reacts on the
rising edge of signal applied.
[68] Timed
Actions
Disabled
Timed actions are disabled. See parameter
group
23-0* Timed Actions
.
[69] Constant OFF
Timed Actions
are set for
Constant OFF
. See
parameter group
23-0* Timed Actions
.
[70] Constant ON
Timed Actions
are set for
Constant ON
. See
parameter group
23-0* Timed Actions
.
[78] Reset
Preventive
Maintenance
Word
Resets all data in
parameter 16-96 Maintenance Word
to 0.
[80] PTC Card 1
ALl digital inputs can be set to
[80] PTC Card
1
. However, only 1 digital input must be set
to this option.
5-10 Terminal 18 Digital Input
The parameter contains all options and functions listed in
parameter group
5-1* Digital Inputs
except for option
[32] Pulse
input
.
5-11 Terminal 19 Digital Input
The parameter contains all options and functions listed in
parameter group
5-1* Digital Inputs
except for option
[32] Pulse
input
.
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described under parameter
group
5-1* Digital Inputs
.
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input
range and the additional options
[60] Counter A (up)
,
[61] Counter A (down)
,
[63] Counter B (up)
and
[64]
Counter B (down)
. Counters are used in smart logic
control functions.
[14]
*
Jog Functions are described under parameter group
5-1*
Digital Inputs
5-14 Terminal 32 Digital Input
The parameter contains all options and functions listed in
parameter group
5-1* Digital Inputs
except for option
[32] Pulse
input
.
5-15 Terminal 33 Digital Input
The parameter contains all options and functions listed in
parameter group
5-1* Digital Inputs
.
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 101 is installed in the frequency
converter. The parameter contains all options
and functions listed in parameter group
5-1*
Digital Inputs
except for option
[32] Pulse
input
.
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 101 is installed in the frequency
converter. The parameter contains all options
and functions listed in parameter group
5-1*
Digital Inputs
except for option
[32] Pulse
input
.
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 101 is installed in the frequency
converter. The parameter contains all options
and functions listed in parameter group
5-1*
Digital Inputs
except for option
[32] Pulse
input
.
5-19 Terminal 37 Safe Stop
Use this parameter to configure the Safe Torque Off functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the
VLT
®
PTC Thermistor Card MCB 112
is
mounted, configure the PTC options to get the full benefit from
the alarm handling.
Option:
Function:
[1]
Safe Stop Alarm Coasts frequency converter when
Safe Torque Off is activated. Manual
reset from LCP, digital input, or
fieldbus.
[3]
Safe Stop
Warning
Coasts the frequency converter when
Safe Torque Off is activated (terminal
37 off). When the safe-stop circuit is
re-established, the frequency
converter continues without manual
reset.
[4]
PTC 1 Alarm
Coasts frequency converter when
Safe Torque Off is activated. Manual
reset from LCP, digital input, or
fieldbus.
[5]
PTC 1 Warning
Coasts frequency converter when
Safe Torque Off is activated (terminal
37 off). When Safe Torque Off circuit
is re-established, the frequency
Parameter Descriptions
VLT
®
HVAC Drive FC 102
72