Log
To see an overview of fire mode-related events, view the fire mode-log, 18-1*, Fire mode log, or press [Alarm Log] on the
LCP or via the Alarm Log button on the LCP.
The log includes up to 10 of the latest events. Warranty-affecting alarms have a higher priority than the other 2 types of
events.
The log cannot be reset
Following events are logged:
•
Warranty-affecting alarms (see
parameter 24-09 Fire Mode Alarm Handling
•
Fire mode activated
•
Fire mode deactivated
All other alarms occurring while fire mode is activated are logged as usual.
NOTICE
During fire mode-operation, all stop commands to the frequency converter are ignored, including coast/coast inverse
and external interlock. However, if Safe Torque Off is available in the frequency converter, this function is still active.
NOTICE
If using the live zero-function in fire mode, then it is also active for analog inputs other than that used for fire mode
setpoint/feedback. Should the feedback to any of those other analog inputs be lost, for example a cable is burned, live
zero-function operates. If this is not wanted, disable the live zero-function for those other inputs.
Set the wanted live zero-function in case of a missing signal when fire mode active in
Warning for live zero has a higher priority than the warning
Fire Mode
.
NOTICE
If setting the command
[11] Start Reversing
on a digital input terminal in
parameter 5-10 Terminal 18 Digital Input
, the
frequency convertor understands this as a reversing command.
24-00 Fire Mode Function
Option:
Function:
NOTICE
In the above, alarms are produced or
ignored in accordance with the
selection in
.
[0]
*
Disabled
Fire mode-function is not active.
[1]
Enabled-
Run
Forward
In this mode the motor continues to operate
in a clockwise direction. Works only in open
loop. Set
parameter 24-01 Fire Mode Configu-
to
[0] Open Loop
.
[2]
Enabled-
Run
Reverse
In this mode the motor continues to operate
in a counterclockwise direction. Works only in
open loop. Set
to
[0] Open Loop
.
[3]
Enabled-
Coast
In this mode, the output is disabled and the
motor is allowed to coast to stop.
[4]
Enabled-
Run
Fwd/Rev
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
185