4 Mechanical Installation
4.1 Items Supplied
Items supplied can vary according to product configu-
ration.
•
Make sure the items supplied and the information
on the nameplate correspond to the order confir-
mation.
•
Visually check the packaging and the drive for
damage caused by inappropriate handling during
shipment. File any claim for damage with the
carrier. Retain damaged parts for clarification.
OUT: 3x0-Vin 0-590Hz 880/780 A
IN: 3x380-480V 50/60Hz 848/752 A
500 kW / 650 HP
VLT
T/C: FC-102N500T4E20H2XGC7XXSXXXXAXBXCXXXXDX
P/N: 135N6991 S/N:
R
HVAC Drive
www.danfoss.com
130BF711.10
ASSEMBLED IN USA
Max Tamb. 55
C/131
F at Full Output Current Derating
Tamb. 40
C/104
F at Full Output Current
SCCR 100 kA at UL Voltage range 380-480 V
Listed 36U0 E70524 IND. CONT. EQ.
UL Voltage range 380-480 V
CAUTION - ATTENTION:
Stored charge, wait 40 min.
Charge residuelle, attendez 40
See manual for special condition / prefuses
Voir manuel de conditions speciales / fusibles
WARNING - AVERTISSEMENT:
`
`
123456H123
1
2
3
4
5
6
Danfoss A/S
6340 Nordborg
Denmark
CHASSIS/IP20
1
Type code
2
Code number
3
Power rating
4
Input voltage, frequency, and current (at low/high
voltages)
5
Output voltage, frequency, and current (at low/high
voltages)
6
Discharge time
Illustration 4.1 Product Nameplate for E4h Enclosure (Example)
NOTICE
Removing the nameplate from the drive can result in the
loss or warranty.
4.2 Tools Needed
Receiving/unloading
•
I-beam and hooks rated to lift the weight of the
drive. Refer to
chapter 3.2 Power Ratings, Weights,
.
•
Crane or other lifting aid to place the unit into
position.
Installation
•
Drill with 10 mm or 12 mm drill bits.
•
Tape measurer.
•
Various sizes of Phillips and flat bladed
screwdrivers.
•
Wrench with relevant metric sockets (7–17 mm).
•
Wrench extensions.
•
Torx drives (T25 and T50).
•
Sheet metal punch for conduits or cable glands.
•
I-beam and hooks to lift the weight of the drive.
Refer to
chapter 3.2 Power Ratings, Weights, and
.
•
Crane or other lifting aid to place the drive onto
pedestal and into position.
4.3 Storage
Store the drive in a dry location. Keep the equipment
sealed in its packaging until installation. Refer to
chapter 9.4 Ambient Conditions
for recommended ambient
temperature.
Periodic forming (capacitor charging) is not necessary
during storage unless storage exceeds 12 months.
Mechanical Installation
VLT® HVAC Drive FC 102
12
Danfoss A/S © 01/2017 All rights reserved.
MG16O102
4
4