Line Power Supply 3 x 525–690 V AC
P710
P800
P900
P1M0
P1M2
P1M4
Typical shaft output at 550 V [kW]
560
670
750
850
1000
1100
Typical shaft output at 575 V [hp]
750
950
1050
1150
1350
1550
Typical shaft output at 690 V [kW]
710
800
900
1000
1200
1400
Enclosure protection ratings IP21, IP54
without/with options cabinet
F1/F3
F1/F3
F1/F3
F2/F4
F2/F4
F2/F4
Output current
Continuous (at 550 V) [A]
763
889
988
1108
1317
1479
Intermittent (60 s overload, at 550 V) [A]
839
978
1087
1219
1449
1627
Continuous (at 575/690 V) [A]
730
850
945
1060
1260
1415
Intermittent (60 s overload, at 575/690 V)
[A]
803
935
1040
1166
1386
1557
Continuous KVA (at 550 V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA (at 575 V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA (at 690 V) [KVA]
872
1016
1129
1267
1506
1691
Maximum input current
Continuous (at 550 V) [A]
743
866
962
1079
1282
1440
Continuous (at 575 V) [A]
711
828
920
1032
1227
1378
Continuous (at 690 V) [A]
711
828
920
1032
1227
1378
Maximum cable size, motor [mm
2
(AWG
2)
)]
8x150 (8x300 mcm)
12x150 (12x300 mcm)
Maximum cable size, line power F1/F2
[mm
2
(AWG
2)
)]
8x240 (8x500 mcm)
Maximum cable size, line power F3/F4
[mm
2
(AWG
2)
)]
8x456 (8x900 mcm)
Maximum cable size, load sharing [mm
2
(AWG
2)
)]
4x120 (4x250 mcm)
Maximum cable size, brake [mm
2
(AWG
2)
)
4x185 (4x350 mcm)
6x185 (6x350 mcm)
Maximum external pre-fuses [A]
1)
1600
2000
2500
Estimated power loss at rated maximum
load [W]
3)
, 600 V, F1 & F2
9500
10872
12316
13731
16190
18536
Estimated power loss at rated maximum
load [W]
3)
, 690 V, F1 & F2
9863
11304
12798
14250
16821
19247
Maximum added losses of circuit breaker
or disconnect & contactor, F3 & F4
427
532
615
665
863
1044
Maximum panel options losses
400
Weight, enclosure protection ratings IP21,
IP54 [kg (lb)]
1004/1299
(2213.5/2863.8
)
1004/1299
(2213.5/2863.8
)
1004/1299
(2213.5/2863.8)
1246/1541
(2747/3397.4)
1246/1541
(2747/3397.4)
1280/1575
(2822/3472.3)
Weight, rectifier module [kg (lb)]
102 (224.9)
102 (224.9)
102 (224.9)
136 (300)
136 (300)
136 (300)
Weight, inverter module [kg (lb)]
102 (224.9)
102 (224.9)
136 (300)
102 (224.9)
102 (224.9)
136 (300)
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemperature trip
95
°
C (203 °F)
105
°
C (221 °F) 95
°
C (203 °F)
95
°
C (203 °F) 105
°
C (221
°F)
95
°
C (203 °F)
Power card ambient trip
85
°
C (185 °F)
Table 7.4 Line Power Supply 3 x 525–690 V AC
1) For type of fuse, see
.
2) American wire gauge.
General Specifications
Instruction Manual
MG11F522
Danfoss A/S © 08/2014 All rights reserved.
121
7
7
Summary of Contents for VLT HVAC Drive FC 102