5.1.16 22-** Appl. Functions
Par.
No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
22-4* Sleep Mode
22-40 Minimum Run Time
10 s
All set-ups
TRUE
0
Uint16
22-41 Minimum Sleep Time
10 s
All set-ups
TRUE
0
Uint16
22-43 Wake-Up Speed [Hz]
10 N/A
All set-ups
TRUE
-1
Uint16
22-44 Wake-Up Ref./FB Diff
10 %
All set-ups
TRUE
0
Uint8
22-45 Setpoint Boost
0 %
All set-ups
TRUE
0
Int8
22-46 Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-47 Sleep Speed [Hz]
0 N/A
All set-ups
TRUE
-1
Uint16
22-6* Broken Belt Detection
22-60 Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61 Broken Belt Torque
10 %
All set-ups
TRUE
0
Uint8
22-62 Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
Table 5.17
5.1.17 24-** Appl. Functions 2
Par.
No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
24-0* Fire Mode
24-00 FM Function
[0] Disabled
1 set-up
TRUE
-
Uint8
24-05 FM Preset Reference
0 %
All set-ups
TRUE
0
Int16
24-09 FM Alarm Handling
[1] Trip, Crit.Alarms
1 set-up
FALSE
-
Uint8
24-1* Drive Bypass
24-10 Drive Bypass Function
[0] Disabled
1 set-up
TRUE
-
Uint8
24-11 Drive Bypass Delay Time
0 s
1 set-up
TRUE
0
Uint16
Table 5.18
Parameter Lists
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
5-15