1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
6.2 EMC Emission Test Results
The following test results have been obtained using a system with a drive, a shielded control cable, a control box with potentiometer,
and a shielded motor cable.
Table 28: EMC Emission Test Results
RFI filter
type
Conduct emission. Maximum shielded cable length [m (ft)]
Radiated emission
Industrial environment
EN 55011
Class A Group 2
Industrial environ-
ment
Class A Group 1
Industrial environ-
ment
Class B
Housing, trades and
light industries
Class A Group 1
Industrial environ-
ment
Class B
Housing, trades
and light industries
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Without
external
filter
With
exter‐
nal fil‐
ter
Without
external
filter
With
exter‐
nal fil‐
ter
Without
external
filter
With
exter‐
nal fil‐
ter
With‐
out ex‐
ternal
filter
With
exter‐
nal fil‐
ter
With‐
out ex‐
ternal
filter
With
exter‐
nal fil‐
ter
H4 RFI filter (EN55011 A1, EN/IEC61800-3 C2)
0.25–11 kW
(0.34–15 hp)
3x200–240 V
IP20
–
–
25 (82)
50 (164)
–
20 (66)
Yes
Yes
–
No
0.37–22 kW
(0.5–30 hp)
3x380–480 V
IP20
–
–
25 (82)
50 (164)
–
20 (66)
Yes
Yes
–
No
H2 RFI filter (EN 55011 A2, EN/IEC 61800-3 C3)
15–45 kW
(20–60 hp)
3x200–240 V
IP20
25 (82)
–
–
–
–
–
No
–
No
–
30–90 kW
(40–120 hp)
3x380–480 V
IP20
25 (82)
–
–
–
–
–
No
–
No
–
0.75–18.5 kW
(1–25 hp)
3x380–480 V
IP54
25 (82)
–
–
–
–
–
Yes
–
–
–
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 73
Danfoss A/S © 2019.11
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 1: ...Operating Guide VLT HVAC Basic Drive FC 101...
Page 2: ......