Table 15: Option:
[0] Resume
Resumes operation of the drive, maintaining the same local reference and the same start/stop condition (ap-
plied by [Hand On]/[Off] on the LCP or local start via a digital input) as before the drive was powered down.
[1] Forced
stop,
ref=old
Uses saved reference [1] to stop the drive, but at the same time retains the local speed reference in memory
before powering down. After mains voltage is reconnected, and after receiving a start command (pressing
[Hand On] key or using the local start command via a digital input), the drive restarts and operates at the re-
tained speed reference.
0-06 GridType
Default value: [Configuration dependent]
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Select the grid type of the supply voltage/frequency.
N O T I C E
Not all options are supported in all power sizes.
IT Grid is a supply mains, where there are no connections to ground.
Delta is a supply mains where the secondary part of the transformer is delta connected and 1 phase is connected to ground.
Table 16: Option:
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[110]
380-440V/60Hz/IT-grid
[111]
380-440V/60Hz/Delta
[112]
380-440V/60Hz
[120]
440-480V/60Hz/IT-grid
[121]
440-480V/60Hz/Delta
[122]
440-480V/60Hz
0-07 Auto DC Braking
Default value: [1] On
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Protective function against over voltage at coast in IT grid environment. This parameter is active only when
[1] On
is selected in this
parameter, and IT-grid options are selected in
parameter 0-06 GridType
.
Table 17: Option:
[0]
Off
This function is not active.
[1]
On
This function is active.