Field name
Example (hex)
Write byte count
04
Write registers value HI
00
Write registers value LO
00
Write registers value HI
02
Write registers value LO
0E
Error check (CRC)
–
Response
The normal response contains the data from the group of registers that were read. The byte count field specifies the quantity of
bytes to follow in the read data field.
Table 83: Response
Field name
Example (hex)
Follower address
01
Function
17
Byte count
04
Read registers value HI
00
Read registers value LO
00
Read registers value HI
C3
Read registers value LO
50
Error check (CRC)
–
8.11 Danfoss FC Control Profile
8.11.1 Control Word According to FC Profile (8-10 Protocol = FC Profile)
Speed ref.
CTW
Master-follower
e
3
0
b
a
2
7
4
.1
1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Illustration 78: Control Word According to FC Profile
Table 84: Control Word According to FC Profile
Bit
Bit value = 0
Bit value = 1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
AJ363928382091en-000101 / 130R0983 | 125
Danfoss A/S © 2021.04
RS485 Installation and Set-up
VLT® Flow Drive FC 111
Design Guide