Bus ad-
dress
Bus
regis-
ter
(1)
PLC reg-
ister
Content
Access
Description
3
4
40004
Free
–
–
4
5
40005
Free
–
–
5
6
40006
Modbus configu-
ration
Read/Write
TCP only. Reserved for Modbus TCP (
parameter 12-28
Store Data Values
and
parameter 12-29 Store Always
-
stored in, for example, EEPROM).
6
7
40007
Last fault code
Read only
Fault code received from parameter database, refer to
WHAT 38295 for details.
7
8
40008
Last error register
Read only
Address of register with which last error occurred, refer
to WHAT 38296 for details.
8
9
40009
Index pointer
Read/Write
Subindex of parameter to be accessed. Refer to WHAT
38297 for details.
9
10
40010
Parameter 0-01
Language
Dependent on
parameter ac-
cess
Parameter 0-01 Language
(Modbus register = 10 param-
eter number) 20 bytes space reserved for parameter in
Modbus map.
19
20
40020
Free
–
–
29
30
40030
Parameter 0-03
Regional Settings
Dependent on
parameter ac-
cess
Parameter 0-03 Regional Settings
20 bytes space re-
served for parameter in Modbus map.
1
Value written in the Modbus RTU telegram must be 1 or less than the register number. For example, Read Modbus Register 1 by writing value 0 in
the telegram.
8.8.9 Access via PCD Write/read
The advantage of using the PCD write/read configuration is that the controller can write or read more data in 1 telegram. Up to 63
registers can be read or written to via the function code read holding register or write multiple registers in 1 telegram. The structure
is also flexible so that only 2 registers can be written to and 10 registers can be read from the controller.
The PCD write list is data sent from the controller to the drive, the data includes control word, reference, and application dependent
data like minimum reference and ramp times, and so on.
N O T I C E
The control word and reference is always sent in the list from the controller to the drive.
The PCD write list is set up in
parameter 8-42 PCD Write Configuration
.
The PCD read list is data sent from the drive to the controller like status word, main actual value, and application dependent data
like running hours, motor current, and alarm word.
N O T I C E
The status word and main actual value is always sent in the list from the drive to the controller.
AJ363928382091en-000101 / 130R0983
116 | Danfoss A/S © 2021.04
RS485 Installation and Set-up
VLT® Flow Drive FC 111
Design Guide