Table 12: Connected Equipment
Options Definition
1
IEC/EN 61000-3-2 Class A for 3-phase balanced equipment (for professional equipment only up to 1 kW (1.3 hp) total
power).
2
IEC/EN 61000-3-12 Equipment 16–75 A and professional equipment as from 1 kW (1.3 hp) up to 16 A phase current.
3.4.4.2 Harmonics Test Results (Emission)
Power sizes up to 10 kW (15 hp) [200–240 V AC] comply with IEC/EN 61000-3-12, Table 4. Power sizes up to 30 kW (40 hp) [380–
480 V AC] comply with IEC/EN 61000-3-2 Class A and IEC/EN 61000-3-12, Table 4.
Table 13: Harmonic Current 6.0–10 kW (8.0–15 hp), 200 V
Individual harmonic current I
n
/I
1
(%)
I
5
I
7
I
11
I
13
Actual 6.0–10 kW (8.0–15 hp), IP20, 200 V (typical)
32.6
16.6
8.0
6.0
Limit for R
sce
≥120
40
25
15
10
Harmonic current distortion factor (%)
THDi
PWHD
Actual 6.0–10 kW (8.0–15 hp), 200 V (typical)
39
41.4
Limit for R
sce
≥120
48
46
Table 14: Harmonic Current 6.0–22 kW (8.0–30 hp), 380–480 V
Individual harmonic current I
n
/I
1
(%)
I
5
I
7
I
11
I
13
Actual 6.0–22 kW (8.0–30 hp), IP20, 380–480 V (typical)
36.7
20.8
7.6
6.4
Limit for R
sce
≥120
40
25
15
10
Harmonic current distortion factor (%)
THDi
PWHD
Actual 6.0–22 kW (8.0–30 hp), 380–480 V (typical)
44.4
40.8
Limit for R
sce
≥120
48
46
Table 15: Harmonic Current 30 kW (40 hp), 380–480 V
Individual harmonic current I
n
/I
1
(%)
I
5
I
7
I
11
I
13
Actual 30 kW (40 hp), IP20, 380–480 V (typical)
36.7
13.8
6.9
4.2
Limit for R
sce
≥120
40
25
15
10
Harmonic current distortion factor (%)
THDi
PWHD
Actual 30 kW (40 hp), 380–480 V (typical)
40.6
28.8
AJ363928382091en-000101 / 130R0983 | 35