Drive
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Output current at 40°C (104°F) ambient temperature
(1)
Continuous [A]
37.0
42.5
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent (110% overload 60
s) [A]
(2)
40.7
46.8
67.1
80.3
99.0
116.0
161.0
194.0
Maximum input current
Continuous [A]
35.2
41.5
57.0
70.0
84.0
103.0
140.0
166.0
Intermittent [A]
38.7
45.7
62.7
77.0
92.4
113.0
154.0
182.0
Maximum external mains fuses
[A]
See
6.9.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W]
(3)
456
523
733
922
1067
1133
1733
2141
Weight enclosure protection
rating IP20 [kg (lb)]
9.5 (20.9)
9.5 (20.9)
24.5 (54)
24.5 (54)
24.5 (54)
36.0
(79.4)
36.0
(79.4)
51.0
(112.4)
Efficiency [%]
(4)
97.9
97.9
97.8
97.7
98
98.2
97.8
97.9
1
Refer to the
chapter Derating
for the derating curves at 50°C (122°F) ambient temperature.
2
The drive also supports 150% overload for 60 s when selecting 1 level higher power size.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
4
Efficiency measured at nominal current. For energy efficiency class, see
9.2.13 Ambient Conditions (H1–H8)
. For part load losses, see Danfoss
website.
Table 90: 3x380–480 V AC, 110–315 kW (150–450 hp), Enclosure Sizes H13–H14
Drive
P110
P132
P160
P200
P250
P315
Typical shaft output [kW]
110
132
160
200
250
315
Typical shaft output [hp]
150
175
250
300
350
450
Protection rating IP20
H13
H13
H13
H14
H14
H14
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
2x95 (2x3/0)
2x185 (2x350 mcm)
Output current at 40°C/45°C (104°F/113°F) ambient temperature
(1)
Continuous [A]
212
260
315
395
480
588
Intermittent (110% overload 60 s)
[A]
(2)
233
286
347
435
528
647
Maximum input current
Continuous [A]
204
251
304
381
463
567
Intermittent [A]
224
276
334
419
509
623
Maximum external mains fuses
[A]
See
6.9.5 Recommendation of Fuses and Circuit Breakers
.
Estimated power loss [W]
(3)(4)
2559
2954
3770
4116
5137
6674
Efficiency
(4)
0.98
AJ363928382091en-000101 / 130R0983
132 | Danfoss A/S © 2021.04
General Specifications
VLT® Flow Drive FC 111
Design Guide