control can only be selected in the
Flux with motor
feedback
(
1-01 Motor Control Principle
) configuration. When
this mode has been selected, the reference uses the Nm
unit. It requires no torque feedback, since the actual
torque is calculated based on the current measurement of
the frequency converter.
Select
[3] Process
in
1-00 Configuration Mode
to use the
process PID control for closed loop control of a process
variable (for example, speed) in the controlled application.
4.6 Local (Hand On) and Remote (Auto)
Control
The frequency converter can be operated manually via the
local control panel (LCP) or remotely via analog and digital
inputs and serial bus. If allowed in
0-40 [Hand on] Key on
LCP
,
0-41 [Off] Key on LCP
,
0-42 [Auto on] Key on LCP
, and
0-43 [Reset] Key on LCP
, it is possible to start and stop the
frequency converter via the LCP using the [Hand On] and
[Off] keys. Alarms can be reset via the [Reset] key. After
pressing the [Hand On] key, the frequency converter goes
into Hand mode and follows (as default) the Local
reference that can be set using arrow key on the LCP.
After pressing the [Auto On] key, the frequency converter
goes into Auto mode and follows (as default) the remote
reference. In this mode, it is possible to control the
frequency converter via the digital inputs and various serial
interfaces (RS-485, USB, or an optional fieldbus). See more
about starting, stopping, changing ramps and parameter
set-ups and so on, in parameter group 5-1* (digital inputs)
or parameter group 8-5* (serial communication).
130BP046.10
Hand
on
Off
Auto
on
Reset
Illustration 4.18 LCP Keys
Active Reference and Configuration Mode
The active reference can be either the local reference or
the remote reference.
In
3-13 Reference Site
the local reference can be
permanently selected by selecting
[2] Local
.
For permanent setting of the remote reference, select
[1]
Remote
. By selecting
[0] Linked to Hand/Auto
(default) the
reference site links to the active mode. (Hand Mode or
Auto Mode).
Remote
reference
Local
reference
Auto mode
Hand mode
Linked to hand/auto
Local
Remote
Reference
130BA245.11
LCP Hand on,
off and auto
on keys
P 3-13
Reference site
Illustration 4.19 Local Reference Handling
Torque
Speed open/
closed loop
Scale to
RPM or
Hz
Scale to
Nm
Scale to
process
unit
Process
closed loop
Local
ref.
Local
reference
Configuration
mode
Local
configuration
mode
130BA246.10
P 1-00
P 1-05
Illustration 4.20 Remote Reference Handling
LCP Keys
3-13 Reference
Site
Active Reference
Hand
Linked to Hand/
Auto
Local
Hand
⇒
Off
Linked to Hand/
Auto
Local
Auto
Linked to Hand/
Auto
Remote
Auto
⇒
Off
Linked to Hand/
Auto
Remote
All keys
Local
Local
All keys
Remote
Remote
Table 4.25 Conditions for Local/Remote Reference Handling
Application Examples
VLT
®
Decentral Drive FCD 302
64
MG04H102 - VLT
®
is a registered Danfoss trademark
4
4