130BC989.10
L1
L2
L3
PE
Min. 16 mm2
Equalizing cable
Control cables
Earthing rail
Cable insula-
tion stripped
Output con-
tactor etc.
Min. 200mm
between con-
trol cables,
motor cable and
Motor cable
Motor, 3 phases and
PLC etc.
Mains-supply
mains cable
PLC
Protective earth
Reinforced protective earth
Illustration 3.18 EMC-correct Electrical Installation of a Frequency Converter
System Integration
VLT
®
Decentral Drive FCD 302
MG04H102 - VLT
®
is a registered Danfoss trademark
41
3
3