6 Specifications
6.1 Power-dependent Specifications
6.1.1 Mains Supply 3 x 380-480 V AC
Frequency converter
Typical Shaft Output [kW]
HK 37
0.37
HK 55
0.55
HK75
0.75
H1K1
1.1
H1K5
1.5
H2K2
2.2
H3K0
3
H4K0
4
H5K5
5.5
H7K5
7.5
Enclosure IP20
J1
J1
J1
J1
J1
J1
J2
J2
J2
J3
Output current
Shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Continuous (3 x 380-439 V) [A]
1.2
1.7
2.2
3
3.7
5.3
7.2
9
12
15.5
Continuous (3 x 440-480 V) [A]
1.1
1.6
2.1
2.8
3.4
4.8
6.3
8.2
11
14
Intermittent (60 s overload) [A]
1.9
2.7
3.5
4.8
5.9
8.5
11.5
14.4
19.2
24.8
Continuous kVA (400 V AC) [kVA]
0.84
1.18
1.53
2.08
2.57
3.68
4.99
6.24
8.32
10.74
Continuous kVA (480 V AC) [kVA]
0.9
1.3
1.7
2.5
2.8
4.0
5.2
6.8
9.1
11.6
Max. input current
Continuous (3 x 380-439 V) [A]
1.2
1.6
2.1
2.6
3.5
4.7
6.3
8.3
11.2
15.1
Continuous (3 x 440-480 V) [A]
1.0
1.2
1.8
2.0
2.9
3.9
4.3
6.8
9.4
12.6
Intermittent (60 s overload) [A]
1.9
2.6
3.4
4.2
5.6
7.5
10.1
13.3
17.9
24.2
Additional specifications
Max. cable cross section (mains,
motor, brake and load sharing) [mm
2
/
AWG]
2)
4 mm
2
Estimated power loss
at rated max. load [W]
3)
52.4
113.9
150.8
Weight, enclosure IP20
2.3
2.3
2.3
2.3
2.3
2.5
3.6
3.6
3.6
4.1
Efficiency
4)
97.6%
97.9%
98.0%
Table 6.1 Mains Supply 3 x 380-480 V AC - Heavy Duty
1)
Frequency converter
Typical Shaft Output [kW]
H11K
11
H15K
15
H18K
18.5
H22K
22
H30K
30
H37K
37
H45K
45
H55K
55
H75K
75
IP20
J4
J4
J5
J5
J6
J6
J6
J7
J7
Output current
Continuous (3 x 380-439 V) [A]
23
31
37
42.5
Continuous (3 x 440-480 V) [A]
21
27
34
40
Intermittent (60 s overload) [A]
34.5
46.5
55.5
63.8
Continuous kVA (400 V AC) [kVA]
15.94
21.48
25.64
29.45
Continuous kVA 480 V AC) [kVA]
17.5
22.4
28.3
33.3
Max. input current
Continuous (3 x 380-439 V ) [A]
22.1
29.9
35.2
41.5
Continuous (3 x 440-480 V) [A]
18.4
24.7
29.3
34.6
Intermittent (60 s overload) [A]
33.2
44.9
52.8
62.3
Additional specifications
Max. cable size (mains, motor, brake)
[mm
2
/AWG]
2)
16 mm
2
16 mm
2
16 mm
2
16 mm
2
50 mm
2
50 mm
2
50 mm
2
50 mm
2
85 mm
2
Estimated power loss at rated max.
load [W]
3)
331.5
457.7
Weight enclosure IP20 [kg]
9.4
9.5
12.3
12.5
Efficiency
4)
97.8%
97.9%
Table 6.2 Mains Supply 3x380-480 V AC - Heavy Duty
1)
Specifications
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark
67
6
6