5.3.1 Ordering Numbers: Brake Resistors 10%
FC 360
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Code no.
Period
Cable cross
section
2
*
Therm.
relay
Max. brake
torque
with R
rec
*
T4
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm
2
]
[A]
[%]
HK37
0.37
890
1041.98
989
0.030
3000
120
1.5
0.3
139
HK55
0.55
593
693.79
659
0.045
3001
120
1.5
0.4
131
HK75
0.75
434
508.78
483
0.061
3002
120
1.5
0.4
129
H1K1
1.1
288
338.05
321
0.092
3004
120
1.5
0.5
132
H1K5
1.5
208
244.41
232
0.128
3007
120
1.5
0.8
145
H2K2
2.2
139
163.95
155
0.190
3008
120
1.5
0.9
131
H3K0
3
100
118.86
112
0.262
3300
120
1.5
1.3
131
H4K0
4
74
87.93
83
0.354
3335
120
1.5
1.9
128
H5K5
5.5
54
63.33
60
0.492
3336
120
1.5
2.5
127
H7K5
7.5
38
46.05
43
0.677
3337
120
1.5
3.3
132
H11K
11
27
32.99
31
0.945
3338
120
1.5
5.2
130
H15K
15
19
24.02
22
1.297
3339
120
1.5
6.7
129
H18K
18.5
16
19.36
18
1.610
3340
120
1.5
8.3
132
H22K
22
16
18.00
17
1.923
3357
120
1.5
10.1
128
H30K
30
11
14.58
13
2.576
3341
120
2.5
13.3
150
H37K
37
9
11.71
11
3.206
3359
120
2.5
15.3
146
H45K
45
8
9.58
9
3.921
3065
120
4
20
150
H55K
55
6
7.80
7
4.816
3070
120
6
26
150
H75K
75
4
5.68
5
6.612
3231
120
10
36
150
Table 5.4 FC 360 - Mains: 380-480 V (T4), 10% Duty Cycle
Type Code and Selection
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark
65
5
5