[2] *
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
[104]
Sensorless Flow
Requires set up by MCT 10 Set-up Software with sensorless specific plug in.
[105]
Sensorless Pressure
Requires set up by MCT 10 Set-up Software with sensorless specific plug in.
If a feedback is not used, its source must be set to
No Function
[0]. Par. 20-20
deter-
mines how the three possible feedbacks will be used
by the PID Controller.
20-01 Feedback 1 Conversion
Option:
Function:
This meter allows a conversion function to be applied to Feedback 1.
[0] *
Linear
Linear
[0] has no effect on the feedback.
[1]
Square root
Square root
[1] is commonly used when a pressure sensor is used to provide flow feedback
(
(
flow
∝
pressure
)
).
[2]
Pressure to temperature
Pressure to temperature
[2] is used in compressor applications to provide temperature feedback
using a pressure sensor. The temperature of the refrigerant is calculated using the following for-
mula:
Temperature
=
A
2
(
ln
(
Pe
+ 1) −
A
1) −
A
3
,
where A1, A2 and A3 are refrigerant-specific constants. The refrigerant must be selected in
par. 20-30
Refrigerant
Setpoint 3
allow the values of
A1, A2 and A3 to be entered for a refrigerant that is not listed in par. 20-30
Refrigerant
.
[3]
Pressure to flow
Pressure to flow is used in applications where the air flow in a duct is to be controlled. The feed-
back signal is represented by a dynamic pressure measurement (pitot tube).
Flow
=
Duct
Area
×
Dynamic
Pressure
×
Air
Density
Factor
See also par. 20-34
Duct 1 Area [m2]
through par. 20-38
Air Density Factor [%]
for setting of
duct area and air density.
[4]
Velocity to flow
Velocity to flow is used in applications where the air flow in a duct is to be controlled. The feed-
back signal is represented by an air velocity measurement.
Flow
=
Duct
Area
×
Air
Velocity
See also par. 20-34
Duct 1 Area [m2]
through par. 20-37
Duct 2 Area [in2]
for setting of duct
area.
6 How to Programme
VLT HVAC Drive High Power Operating In-
structions
122
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
6