Ref./Feedback
[RPM]
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
130BA038.13
1 V
5 V
10 V
300
600
900
1200
1500
[V]
150
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V*
[ 0.00 - par. 6-11 V]
Enter the low voltage value. This analog input scaling value should correspond to the low refer-
ence/feedback value set in par. 6-14
Terminal 53 Low Ref./Feedb. Value
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V*
[ par. 6-10 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-15
Terminal 53 High Ref./Feedb. Value
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 *
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the low voltage/low current set in
par. 6-10
Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Size rela-
ted*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par. 6-11
and par. 6-13
Terminal 53 High Current
.
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor
is running.
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
117
6