2.3.6 Quick Menu Motor Set-up
The Quick Menu Motor Set-up guides the installer through setting of the required motor parameters.
NOTICE
MOTOR OVERLOAD PROTECTION
Thermal protection of the motor is recommended. Especially when running at low speed, the cooling from the
integrated motor fan is often not sufficient.
•
Use PTC. See
chapter Motor Connection
in
VLT
®
DriveMotor FCP 106/FCM 106 Operating Instructions
, or
•
Enable motor thermal protection by setting
parameter 1-90 Motor Thermal Protection
to
[4] ETR trip 1
.
Asynchronous Motor
1-73 Flying Start
[0]
No
1-22 Motor Voltage
400
V
1-24 Motor Current
04.66
A
1-25 Motor nominal speed
1420
RPM
3-41 Ramp 1 ramp-up time
0003
s
3-42 Ramp1 ramp-down time
0003
s
0-06 Grid Type
4-12 Motor speed low limit
0016
Hz
4-13 Motor speed high limit
0050
Hz
195NA462.11
1-20 Motor Power
1.10
kW
1-23 Motor Frequency
50
Hz
1-00
[3]
Closed Loop
0-03 Regional Settings
[0]
International
1-10 Motor Type
[0]
Asynchronous
[12]]
1-30 Stator Resistance
0.65
Ohms
1-25 Motor Nominal Speed
3000
RPM
1-24 Motor Current
3.8
A
1-26 Motor Cont. Rated Torque
5.4
Nm
1-38 q-axis inductance(Lq)
5
mH
4-19 Max Ouput Frequency
0065
Hz
1-40 Back EMF at 1000 RPM
57
V
PM Motor
1-39 Motor Poles
8
MotorType = Asynchronous
MotorType = PM Motor
Motor Type = IPM
IPM Type = Sat.
IPM Type = non-Sat.
1-44 d-axis Inductance Sat. (LdSat)
(1-70) PM Start Mode
Rotor Detection
[0]
1-46 Position Detection Gain
%
100
30-22 Locked Rotor Detection
[0]
s
30-23 Locked Rotor Detection Time[s]
0.10
5
mH
(1-45) q-axis Inductance Sat. (LqSat)
5
mH
(1-48) Current at Min Inductance for d-axis
100
%
1-49 Current at Min Inductance for q-axis
100
%
380-440V/50Hz
Illustration 2.5 Quick Menu Motor Set-up
Programming
VLT
®
DriveMotor FCP 106/FCM 106
12
Danfoss A/S © 11/2015 All rights reserved.
MG03N202