Decentral Solutions
Programming, FCD
300
■
The LCP 2 control unit, option
The FCD 300 can be combined with an LCP control
unit (Local Control Panel - LCP 2) which makes up a
complete interface for operation and programming of
the variable frequency drive. The LCP 2 control unit can
be attached up to nine feet from the variable frequency
drive, e.g. on a front panel, using an accessory kit.
The control panel is divided into five functional groups:
1. Display.
2. Keys used to change the display function.
3. Keys used to change the program parameters.
4. LEDs.
5. Local control keys.
All data is displayed via a 4-line alphanumeric
display, which during normal operation will be able
to continuously display 4 items of operating data
and 3 operating modes. During programming all
information needed for quick, effective parameter setup
of the variable frequency drive will be displayed. As
a supplement to the display, there are three LEDs for
voltage (ON), warning (WARNING) and alarm (ALARM).
All variable frequency drive parameter Setups can be
changed immediately from the control panel, unless
this function has been programmed as
Locked
[1]
via parameter 018
Lock for data changes
.
■
Control keys for parameter Setup
The control keys are divided into functions, in such a
way that the keys between the display and the indicator
lamps are used for parameter Setup, including selection
of the display
’
s view mode during normal operation.
[DISPLAY/STATUS]
is used to select the display
’
s
view mode or to change back to Display mode
from either Quick Menu or Menu mode.
[QUICK MENU]
provides access to the parameters
used in the Quick Menu. It is possible to switch
between Quick Menu and Menu mode.
[MENU]
gives access to all parameters. It is possible
to switch between Menu mode and Quick Menu.
[CHANGE DATA]
is used to change a parameter that
has been selected either in Menu mode or Quick Menu.
[CANCEL]
is used if a change to the selected
parameter is not to be implemented.
[OK]
is used to confirm a change to a
selected parameter.
[+ / -]
are used for selecting parameters and
for changing parameter values.
These keys are also used in Display mode to switch
between the readouts of operating variables.
[< >]
are used for selecting parameter group and to
move the cursor when changing a numerical value.
MG.90.F2.22 - VLT is a registered Danfoss trademark
93