Decentral Solutions
Specification and
order codes, DMS 300
■
Details of Profibus Connectivity
NOTE
When using Profibus interface, the complete
control of the DMS is done by the Profibus. The
DMS control terminals cannot be used.
■
Profibus DP Slave 6 E/DC 24 V, 4 A/DC 24 V/1A
connection
bus connection
spring terminal block 2 x 2 x 0.1 sq.in. (2.5
sq.mm.)
69: A-Line RxD/TxD-N, green wire 68:B-Line
RxD/TxD-P, red wire
termination
switchable, SW2 both on
supply power to the
module
voltage range incl. ripple
20-30VDC
ripple
max. 10%
current consumption
nom. 90 mA
connection
spring terminal block 2 x 2 x 0.1 sq.in. (2.5
sq.mm.)
201: DC 0 V, 202:DC 24 V
supply power input and
output
voltage range incl. ripple
20-30VDC
connection
spring terminal block 2 x 2 x 0.1 sq.in. (2.5
sq.mm.)
203: DC 0 V, 204:DC 24 V
galvonic isolation
isolation voltage
DC 500 V between bus and electronics
DC 2.5kV between module supply and
inputs/ outputs
Bus interface
Bus system
Profibus DP
module type
Slave I/O module
standard
DIN 19245
data width in the process image
1 Byte inputs, 1 Byte outputs
fieldbus controller
LSPM2
identifier
0409 hex
addressing
Node ID: 1-99 set by DIP switch SW3
baud rate
up to 12Mbaud, automatic detection
MG.90.F2.22 - VLT is a registered Danfoss trademark
59