10-15 Net Control
Read only from LCP.
Option: Function:
Select the control source in instances 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1]
On Enable control via the fieldbus.
10-20 COS Filter 1
Range:
Function:
0
*
[0 - 65535] Sets up the filter mask for the status word.
When operating in COS (change-of-state), it is
possible to filter out bits in the status word that
should not be sent if they change.
10-21 COS Filter 2
Range:
Function:
0
*
[0 - 65535] Sets up the filter mask for the main actual
value. When operating in COS (change-of-state),
it is possible to filter out bits in the main actual
value that should not be sent if they change.
10-22 COS Filter 3
Range:
Function:
0
*
[0 - 65535] Sets up the filter mask for PCD 3. When
operating in COS (change-of-state), it is possible
to filter out bits in PCD 3 that should not be
sent if they change.
10-23 COS Filter 4
Range:
Function:
0
*
[0 - 65535] Sets up the filter mask for PCD 4. When
operating in COS (change-pf-state), it is possible
to filter out bits in PCD 4 that should not be
sent if they change.
10-30 Array Index
Range:
Function:
0
*
[0 - 255 ] View array parameters. This parameter is valid
only when a VLT
®
DeviceNet MCA 104 is installed.
10-31 Store Data Values
Option:
Function:
This parameter is used to activate a function that
stores all parameter values in the non-volatile
memory thus retaining changed parameter
values at power down.
[0] Off
The store function is inactive.
[1] Store all
setups
All parameter values in the set-up selected are
stored in the non-volatile memory.
The value returns to
[0] Off
when all values are
stored.
10-31 Store Data Values
Option:
Function:
[2] Store all
setups
All parameter values are stored in the non-
volatile memory. The value returns to
[0] Off
when all parameter values are stored.
10-32 Devicenet Revision
Range:
Function:
0
*
[0 - 65535 ] View the DeviceNet revision number. This
parameter is used for EDS file creation.
10-33 Store Always
This parameter is used to select whether parameter data received
via the DeviceNet option should always be stored in non-volatile
memory.
Option:
Function:
[0]
*
Off
[1]
On
10-34 DeviceNet Product Code
Range:
Function:
Size related
*
[0 - 65535]
16-90 Alarm Word
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-91 Alarm Word 2
Range:
Function:
0
*
[0 - 4294967295] View the alarm word sent via the serial
communication port in hex code.
16-92 Warning Word
Range:
Function:
0
*
[0 - 4294967295 ] View the warning word sent via the serial
communication port in hex code.
16-93 Warning Word 2
Range:
Function:
0
*
[0 - 4294967295] View the warning word sent via the serial
communication port in hex code.
16-94 Ext. Status Word
Range:
Function:
0
*
[0 - 4294967295] Returns the extended warning word sent
via the serial communication port in hex
code.