
11.11.5 Conversion Factor
The different attributes for each parameter can be seen in
the section on factory settings. Since a parameter value
can only be transferred as a whole number, a conversion
factor must be used to transfer decimals. Please refer to
the
Parameters section
.
11.11.6 Parameter Values
Standard Data Types
Standard data types are int16, int32, uint8, uint16 and
uint32. They are stored as 4x registers (40001 – 4FFFF). The
parameters are read using function 03HEX "Read Holding
Registers." Parameters are written using the function 6HEX
"Preset Single Register" for 1 register (16 bits), and the
function 10HEX "Preset Multiple Registers" for 2 registers
(32 bits). Readable sizes range from 1 register (16 bits) up
to 10 registers (20 characters).
Non standard Data Types
Non standard data types are text strings and are stored as
4x registers (40001 – 4FFFF). The parameters are read
using function 03HEX "Read Holding Registers" and written
using function 10HEX "Preset Multiple Registers." Readable
sizes range from 1 register (2 characters) up to 10 registers
(20 characters).
11.12 Danfoss FC Control Profile
11.12.1 Control Word According to FC
Profile (
8-10 Control Profile
= FC
profile)
Speed ref.
CTW
Master-slave
130BA274.10
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Bit
Bit value = 0
Bit value = 1
00
Reference value
external selection lsb
01
Reference value
external selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output
frequency
use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 02 active
13
Parameter set-up
selection lsb
14
Parameter set-up
selection msb
15
No function
Reverse
Explanation of the Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in
3-10 Preset
Reference
according to the following table:
Programmed ref.
value
Parameter
Bit 01
Bit 00
1
3-10 Preset
Reference
[0]
0
0
2
3-10 Preset
Reference
[1]
0
1
3
3-10 Preset
Reference
[2]
1
0
4
3-10 Preset
Reference
[3]
1
1
NOTE
Make a selection in
8-56 Preset Reference Select
to define
how Bit 00/01 gates with the corresponding function on
the digital inputs.
Bit 02, DC brake:
Bit 02 = ’0’ leads to DC braking and stop. Set braking
current and duration in
2-01 DC Brake Current
and
2-02 DC
Braking Time
. Bit 02 = ’1’ leads to ramping.
Bit 03, Coasting:
Bit 03 = ’0’: The frequency converter immediately "lets go"
of the motor, (the output transistors are "shut off") and it
coasts to a standstill. Bit 03 = ’1’: The frequency converter
starts the motor if the other starting conditions are met.
RS-485 Installation and Set...
FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
267
11
11