1-80 Function at Stop
Option:
Function:
current
magnitude
(
or
parameter 2-01 D
C Brake Current
to be equal to
I_pre-mag =
Unom/(1.73 x Xh)
Sample rotor time constants =
(Xh+X2)/(6.3*Freq_nom*Rr)
1 kW = 0.2 s
10 kW = 0.5 s
100 kW = 1.7 s
1000 kW = 2.5 s
[4]
DC Voltage U0 When the motor is stopped, the
parameter 1-55 U/f Characteristic - U
[0] defines the voltage at 0 Hz.
1-81 Min Speed for Function at Stop [RPM]
Range:
Function:
Size
related
*
[0 - 600
RPM]
Set the speed at which to activate
parameter 1-80 Function at Stop
.
1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
Size
related
*
[ 0 - 500.0
Hz]
Set the output frequency at which
to activate
4.2.9 1-9* Motor Temperature
1-90 Motor Thermal Protection
Option:
Function:
Motor thermal protection can be
implemented using a range of
techniques:
•
Via a PTC sensor in the
motor windings connected
to 1 of the analog or
digital inputs
(
). See
chapter 4.2.10 PTC
Thermistor Connection
.
•
Via calculation (ETR =
Electronic Thermal Relay)
of the thermal load, based
on the actual load and
time. The calculated
thermal load is compared
1-90 Motor Thermal Protection
Option:
Function:
with the rated motor
current I
M,N
and the rated
motor frequency f
M,N
. See
.
•
Via a mechanical thermal
switch (Klixon type). See
.
For the North American market: The
ETR functions provide class 20
motor overload protection in
accordance with NEC.
[0]
No protection
Continuously overloaded motor
when no warning or trip of the
frequency converter is required.
[1]
Thermistor
warning
Activates a warning when the
connected thermistor or KTY sensor
in the motor reacts in the event of
motor overtemperature.
[2]
Thermistor trip Stops (trips) the frequency
converter when connected
thermistor or KTY sensor in the
motor reacts in the event of motor
overtemperature.
The thermistor cutout value must
be more than 3 k
Ω
.
Integrate a thermistor (PTC sensor)
in the motor for winding
protection.
[3]
ETR warning 1 Calculates the load when set-up 1
is active and activates a warning on
the display when the motor is
overloaded. Program a warning
signal via 1 of the digital outputs.
[4]
ETR trip 1
Calculates the load when set-up 1
is active and stops (trips) the
frequency converter when the
motor is overloaded. Program a
warning signal via 1 of the digital
outputs. The signal appears in the
event of a warning and if the
frequency converter trips (thermal
warning).
[5]
ETR warning 2
[6]
ETR trip 2
[7]
ETR warning 3
[8]
ETR trip 3
[9]
ETR warning 4
[10]
ETR trip 4
Parameter Descriptions
VLT® AutomationDrive FC 361
46
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4