4.12.1 13-0* SLC Settings
Use the SLC settings to activate, deactivate, and reset the
smart logic control sequence. The logic functions and
comparators are always running in the background, which
opens for separate control of digital inputs and outputs.
13-00 SL Controller Mode
Option:
Function:
[0]
Off
Disables the smart logic controller.
[1]
On
Enables the smart logic controller.
13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
Function:
[0]
False
Select the boolean (true or false)
input to activate smart logic
control.
Enters the fixed value - false.
[1]
True
Enters the fixed value - true.
[2]
Running
The motor runs.
[3]
In range
The motor runs within the
programmed current and speed
ranges set in
parameter 4-50 Warning Current Low
to
[4]
On reference
The motor runs on reference.
[5]
Torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor
Mode
or
is exceeded.
[6]
Current Limit
The motor current limit set in
is
exceeded.
[7]
Out of current
range
The motor current is outside the
range set in
.
[8]
Below I low
The motor current is lower than set
in
parameter 4-50 Warning Current
Low
.
[9]
Above I high
The motor current is higher than
set in
parameter 4-51 Warning
Current High
.
[10]
Out of speed
range
The speed is outside the range set
in
parameter 4-52 Warning Speed
Low
and
[11]
Below speed
low
The output speed is lower than the
setting in
parameter 4-52 Warning
Speed Low
.
13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
Function:
[12]
Above speed
high
The output speed is higher than
the setting in
parameter 4-53 Warning Speed High
[13]
Out of feedb.
range
The feedback is outside the range
set in
parameter 4-56 Warning
Feedback Low
and
parameter 4-57 Warning Feedback
High
.
[14]
Below feedb.
low
The feedback is below the limit set
in
parameter 4-56 Warning Feedback
Low
.
[15]
Above feedb.
high
The feedback is above the limit set
in
parameter 4-57 Warning Feedback
High
.
[16]
Thermal
warning
The thermal warning turns on when
the temperature exceeds the limit
in the motor, the frequency
converter, the brake resistor, or the
thermistor.
[17]
Mains out of
range
The mains voltage is outside the
specified voltage range.
[18]
Reversing
The output is high when the
frequency converter is running
counterclockwise (the logical
product of the status bits running
AND reverse).
[19]
Warning
A warning is active.
[20]
Alarm (trip)
A (trip) alarm is active.
[21]
Alarm (trip
lock)
A (trip lock) alarm is active.
[22]
Comparator 0
Use the result of comparator 0.
[23]
Comparator 1
Use the result of comparator 1.
[24]
Comparator 2
Use the result of comparator 2.
[25]
Comparator 3
Use the result of comparator 3.
[26]
Logic rule 0
Use the result of logic rule 0.
[27]
Logic rule 1
Use the result of logic rule 1.
[28]
Logic rule 2
Use the result of logic rule 2.
[29]
Logic rule 3
Use the result of logic rule 3.
[33]
Digital input
DI18
Use the result of digital input 18.
[34]
Digital input
DI19
Use the result of digital input 19.
[35]
Digital input
DI27
Use the result of digital input 27.
[36]
Digital input
DI29
Use the result of digital input 29.