1-20 Motor Power [kW]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
kW]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the frequency
converter.
This parameter is visible in the LCP if
parameter 0-03 Regional Settings
is set to
[0] International
.
1-21 Motor Power [HP]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
hp]
Enter the nominal motor power in hp
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit. This
parameter is visible in the LCP if
parameter 0-03 Regional Settings
is
[1] US
.
1-22 Motor Voltage
Range:
Function:
Size
related
*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
NOTICE
From software version 6.72 onwards,
the output frequency of the frequency
converter is limited to 590 Hz.
Select the motor frequency value from the
motor nameplate data. If a value other than
50 Hz or 60 Hz is selected, adapt the load-
independent settings in
parameter 1-50 Motor
Magnetisation at Zero Speed
to
parameter 1-53 Model Shift Frequency
. For
87 Hz operation with 230/400 V motors, set
the nameplate data for 230 V/50 Hz. To run at
87 Hz, adapt
parameter 4-13 Motor Speed High
Limit [RPM]
and
parameter 3-03 Maximum
Reference
.
1-23 Motor Frequency
Range:
Function:
50
*
[20 -
1000
Hz]
NOTICE
The default range for the parameter is only
available for software version 8.23.
From software version 6.72 onwards, the
output frequency of the frequency
converter is limited to 590 Hz.
Select the motor frequency value from the motor
nameplate data. If a value other than 50 Hz or 60
Hz is selected, adapt the load-independent settings
in
parameter 1-50 Motor Magnetisation at Zero
Speed
to
parameter 1-53 Model Shift Frequency
. For
87 Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. To run at 87 Hz,
adapt
parameter 4-13 Motor Speed High Limit [RPM]
and
parameter 3-03 Maximum Reference
.
1-24 Motor Current
Range:
Function:
Size
related
*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. The data is used for
calculating torque, motor overload
protection, and so on.
1-25 Motor Nominal Speed
Range:
Function:
Size
related
*
[10 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. The data is used for calculating
motor compensations. n
m,n
= n
s
-
n
slip
.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size
related
*
[0.1 -
100000.0
Nm]
Enter the value from the motor
nameplate data. The default value
corresponds to the nominal rated
output. This parameter is available when
parameter 1-10 Motor Construction
is set
to
[1] PM, non-salient SPM
, that is the
parameter is valid for PM and non-
salient SPM motors only.
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The AMA function optimizes dynamic motor
performance by automatically optimizing the
advanced motor parameters
(
parameter 1-30 Stator Resistance (Rs)
to
Parameter Descriptions
Programming Guide
MG33MP02