6-50 Terminal 42 Output
Option:
Function:
I
VLT
Max
x 100
I
Motor
Norm
= 38 . 4 x 100
22
= 175 %
[134] Torq.% lim
4-20 mA
The torque setting is related to the setting
in
parameter 4-16 Torque Limit Motor Mode
.
[135] Torq.% nom
4-20mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
Taken from
parameter 1-20 Motor Power
[kW]
.
[137] Speed
4-20mA
Taken from
parameter 3-03 Maximum
Reference
. 20 mA = value in
parameter 3-03 Maximum Reference
.
[138] Torque
4-20mA
Torque reference related to 160% torque.
[139] Bus ctrl. 0-20
mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency
converter.
[140] Bus ctrl. 4-20
mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency
converter.
[141] Bus ctrl
0-20mA t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in
case of fieldbus timeout.
[142] Bus ctrl
4-20mA t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in
case of fieldbus timeout.
[147] Main act val
0-20mA
[148] Main act val
4-20mA
[149] Torque %
lim 4-20mA
Analog output at 0 torque is 12 mA.
Motoring torque increases the output
current to maximum torque limit 20 mA (set
in
parameter 4-16 Torque Limit Motor Mode
).
Generating torque decreases the output to
torque limit in generator mode (set in
parameter 4-17 Torque Limit Generator Mode
)
Example:
Parameter 4-16 Torque Limit Motor
Mode
= 200% and
parameter 4-17 Torque
Limit Generator Mode
= 200%. 20 mA =
200% motoring and 4 mA = 200%
generating.
0mA
12 mA
20 mA
4mA
Par 4-17
(200%)
Par 4-16
(200%)
0% Torque
130BB372.10
Illustration 3.44 Torque Limit
[150] Max Out Fr
4-20mA
0 Hz = 0 mA,
parameter 4-19 Max Output
Frequency
= 20 mA.
[158] Motor Volt.
0-20mA
6-50 Terminal 42 Output
Option:
Function:
[159] Motor Volt.
4-20mA
6-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
parameter 6-50 Terminal 42 Output
.
6-52 Terminal 42 Output Max Scale
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal 42. Set the value to the
maximum value of the current signal output.
Scale the output to give a current lower than 20
mA at full scale; or 20 mA at an output below
100% of the maximum signal value. If 20 mA is
the required output current at a value 0–100% of
the full-scale output, program the percentage
value in the parameter, that is 50% = 20 mA. If a
current 4–20 mA is required at maximum output
(100%), calculate the percentage value as follows:
20 mA/desired maximum current x 100 %
i . e . 10 mA : 20
10 x 100 = 200 %
e30ba075.14
(mA)
0%
20
0/4
100%
Current
Analog
output
min scale
par. 6-51
Variable for
output
example:
Speed (RPM)
Analog
output
max scale
par. 6-52
Illustration 3.45 Output Max. Scale
6-53 Term 42 Output Bus Ctrl
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of output 42 if controlled by
bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Holds the preset level of output 42.
If a timeout function is selected in
parameter 6-50 Terminal 42 Output
, the output
is preset to this level if a fieldbus timeout
occurs.
Parameter Descriptions
Programming Guide