NOTICE
When changing the function of S201, S202 or S801 be
careful not to use force for the switch over. It is
recommended to remove the LCP fixture (cradle) when
operating the switches. The switches must not be
operated with power on the frequency converter.
130B
T310.11
Illustration 3.79
3.6 Connection Examples
3.6.1 Start/Stop
Terminal 18 =
5-10 Terminal 18 Digital Input
[8] Start
Terminal 27 =
5-12 Terminal 27 Digital Input
[0] No
operation
(Default
coast inverse
)
Terminal 37 = Safe Torque Off
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 3.80
3.6.2 Pulse Start/Stop
Terminal 18 =
5-10 Terminal 18 Digital Input
[9] Latched
start
Terminal 27=
5-12 Terminal 27 Digital Input
[6] Stop inverse
Terminal 37 = Safe Torque Off
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
Illustration 3.81
3.6.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 =
5-10 Terminal 18 Digital Input
[9]
Start
(default)
Terminal 27 =
5-12 Terminal 27 Digital Input
[19]
Freeze reference
Terminal 29 =
5-13 Terminal 29 Digital Input
[21]
Speed up
Terminal 32 =
5-14 Terminal 32 Digital Input
[22]
Speed down
NOTICE
Terminal 29 only in FC x02 (x=series type).
12
18
27
29
32
37
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
130BA021.12
Illustration 3.82 Speed Up/Down
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
76
MG33U402 - Rev. 2013-12-16
3
3