8.4.3 Supplementary Fuses
Supplementary fuses
Enclosure size
Bussmann PN
Rating
D, E, and F
KTK-4
4 A, 600 V
Table 8.10 SMPS Fuse
Size/Type
Bussmann PN
LittelFuse
Rating
315–630 kW, 380–500 V
KLK-15
15 A, 600 V
Table 8.11 Fan Fuses
Size/Type
Bussmann PN
Rating
Alternative fuses
450–630 kW, 380–500 V 2.5–4.0 A
LPJ-6 SP or SPI
6 A, 600 V
Any listed class J dual
element, time delay, 6A
450–630 kW, 380–500 V 4.0–6.3 A
LPJ-10 SP or SPI
10 A, 600 V
Any listed class J dual
element, time delay, 10 A
450–630 kW, 380–500 V 6.3–10 A
LPJ-15 SP or SPI
15 A, 600 V
Any listed class J dual
element, time delay, 15 A
450–630 kW, 380–500 V 10–16 A
LPJ-25 SP or SPI
25 A, 600 V
Any listed class J dual
element, time delay, 25 A
Table 8.12 Manual Motor Controller Fuses
Enclosure
size
Bussmann PN
1)
Rating
Alternative fuses
F
LPJ-30 SP or SPI
30 A, 600 V
Any listed Class J dual element, time delay, 30 A
Table 8.13 30 A Fuse Protected Terminal Fuse
Enclosure size
Bussmann PN
1)
Rating
Alternative fuses
F
LPJ-6 SP or SPI
6 A, 600 V
Any listed class J dual element, time delay, 6 A
Table 8.14 Control Transformer Fuse
Frame size
Bussmann PN
1)
Rating
F
GMC-800MA
800 mA, 250 V
Table 8.15 NAMUR Fuse
Enclosure size
Bussmann PN
1)
Rating
Alternative fuses
F
LP-CC-6
6 A, 600 V
Any listed class CC, 6 A
Table 8.16 Safety Relay Coil Fuse with PILS Relay
Enclosure size
LittelFuse PN
Rating
D, E, F
KLK-15
15 A, 600 V
Table 8.17 Mains Fuses (Power Card)
Enclosure size
Bussmann PN
Rating
D, E, F
FNQ-R-3
3 A, 600 V
Table 8.18 Transformer Fuse (Mains Contactor)
Specifications
VLT
®
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
104
Danfoss A/S © Rev. 04/2015 All rights reserved.
MG37A322
8
8