Option Name
Description
[0]*
Do not reset
[1]
Reset counter To reset the running hours counter to 0, select
[1] Reset
and press [OK] (see
parameter 15-01 Running
Hours
). This parameter cannot be selected via the serial port, RS485. Select
[0] Do not reset
if no reset of
the running-hours counter is required.
5.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data sources (
parameter 15-10 Logging Source
) at individual rates (
parameter
15-11 Logging Interval
). A trigger event (
parameter 15-12 Trigger Event
) and window (
parameter 15-14 Samples Before Trigger
) are used
to start and stop the logging conditionally.
Parameter 15-10 Logging Source
Table 769: Parameter 15-10 Logging Source
15-10 Logging Source
Default value: [0] None
Parameter type: Option, Array [4]
Setup: 2 setups
Conversion index: -
Data type: Uint16
Change during operation: True
Select the variables to be logged.
Option
Name
Description
[0]*
None
[15]
Readout: Actual setup
[1397]
Alert alarm word
[1398]
Alert warning word
[1399]
Alert status word
[1472]
Legacy alarm word
[1473]
Legacy warning word
[1474]
Leg. ext. status word
[1600]
Control word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status word
[1606]
Actual position
[1607]
Target position
This option is only available with software version 48.XX.
[1608]
Position error
This option is only available with software version 48.XX.
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor voltage
[1613]
Frequency
[1614]
Motor current
AU275636650261en-000101 / 130R0334 | 479
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide