N O T I C E
A lower level than default might cause false alarms as it increases sensitivity.
Parameter 14-18 Fast Mains Phase Loss Min Power
Table 715: Parameter 14-18 Fast Mains Phase Loss Min Power
14-18 Fast Mains Phase Loss Min Power
Default value: 2
Parameter type: Range, 0 - 100
Setup: All setups
Conversion index: -3
Data type: Uint32
Change during operation: True
Set the minimum power level (% of nominal power) at which the functions Fast Mains Phase Loss Trip or Fst Mains Phase Loss Warn-
ing (see
parameter 14-12 Response to Mains Imbalance
) should be activated.
N O T I C E
A minimum power level of 2% is a prerequisite for the Fast Mains Phase Loss function to work.
5.14.3 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling, and control card self-test or initialization.
Parameter 14-20 Reset Mode
Table 716: Parameter 14-20 Reset Mode
14-20 Reset Mode
Default value: [0] Manual reset
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the reset function after tripping. Once reset, the drive can be restarted.
N O T I C E
The motor may start without warning. If the specified number of automatic resets is reached within 10 minutes, the drive enters
[0] Manual reset
mode. After the manual reset is performed, the setting of
parameter 14-20 Reset Mode
returns to the original se-
lection. If the number of automatic resets are not reached within 10 minutes, or when a manual reset is performed, the internal
automatic reset counter returns to 0.
Option
Name
Description
[0]*
Manual reset
Select
[0] Manual reset
to perform a reset via [Reset] or via the digital inputs.
[1]
Automatic reset x 1
Select
[1]
-
[12] Automatic reset
x 1… x20 to perform 1–20 automatic resets after tripping.
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
AU275636650261en-000101 / 130R0334 | 459
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide