Op-
tion
Name
Description
[2]
>
N O T I C E
If
[20] Alarm number
or
[21] Warning number
is selected in
parameter 3-10 Comparator Operand
,
[2] >
cannot be selected in this parameter.
Inverse logic of option
[0] <
.
[5]
TRUE longer
than..
[6]
FALSE longer-
than..
[7]
TRUE shorter
than..
[8]
FALSE shorter
than..
Parameter 13-12 Comparator Value
Table 676: Parameter 13-12 Comparator Value
13-12 Comparator Value
Default value: Size related
Parameter type: Range, -100000.000 - 100000, Array [10]
Setup: 2 setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the trigger level for the variable that is monitored by this comparator. This is an array parameter containing comparator values
0–9.
5.13.2.1 RS FlipFlops
The reset/set flipflops hold the signal until set/reset.
Parameter 13-15
RS-FF Operand S
Parameter 13-16
RS-FF Operand R
e3
0b
b9
59
.1
1
Illustration 80: Reset/Set Flipflops
Two parameters are used and the output can be used in the logic rules and as events.
R
S
Flip flop output
e3
0b
b9
60
.1
1
Illustration 81: Flipflop Outputs
AU275636650261en-000101 / 130R0334
388 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide