4.1.1 Quick Transfer of Parameter Settings between Multiple Drives
When the setup of a drive is completed, store the data in the LCP. Then connect the LCP to another drive and copy the parameter
settings to the new drive.
4.1.1.1 Transferring Data from the Drive to the LCP
Procedure
Go to
parameter 0-50 LCP Copy
.
Press [OK].
Select
[1] All to LCP
.
Press [OK].
4.1.1.2 Transferring Data from the LCP to the Drive
Procedure
Go to
parameter 0-50 LCP Copy
.
Press [OK].
Select
[2] All from LCP
.
Press [OK].
4.1.2 Display Mode
In normal operation, up to 5 different operating variables can be indicated continuously in the middle section: 1.1, 1.2, and 1.3, as
well as 2 and 3.
4.1.3 Display Mode - Selection of Readouts
It is possible to toggle between 3 status readout screens by pressing [Status].
Operating variables with different formatting are shown in each status view (status view I, status view II, status view III).
The following table shows the measurements that can be linked to each of the operating variables. When options are mounted,
additional measurements are available.
Define the links via:
Parameter 0-20 Display Line 1.1 Small.
Parameter 0-21 Display Line 1.2 Small.
Parameter 0-22 Display Line 1.3 Small.
Parameter 0-23 Display Line 2 Large.
Parameter 0-24 Display Line 3 Large.
Each readout parameter selected in
parameter 0-20 Display Line 1.1 Small
to
parameter 0-24 Display Line 3 Large
has its own scale and
digits after a possible decimal point. The larger the numeric value of a parameter is, the fewer digits are shown after the decimal
point.
Example: Current readout 5.25 A, 15.2 A, 105 A.
Table 1: Units
Operating variable
Unit
Parameter 16-00 Control Word
hex
Parameter 16-01 Reference [Unit]
[Unit]
Parameter 16-02 Reference [%]
%
Parameter 16-03 Status Word
hex
Parameter 16-05 Main Actual Value [%]
%
Parameter 16-06 Actual Position
Parameter 16-09 Custom Readout
Parameter 16-10 Power [kW]
[kW]
AU275636650261en-000101 / 130R0334 | 21
Danfoss A/S © 2022.12
How to Program
VLT AutomationDrive FC 301/302
Programming Guide