5.2.10.6 PM Settings
If
[2] Std. PM, non-salient
is selected in
parameter 1-10 Motor Construction
, enter the motor parameters manually in the following
order:
Parameter 1-24 Motor Current
.
Parameter 1-26 Motor Cont. Rated Torque
.
Parameter 1-25 Motor Nominal Speed
.
Parameter 1-39 Motor Poles
.
Parameter 1-30 Stator Resistance (Rs)
.
Parameter 1-37 d-axis Inductance (Ld)
.
Parameter 1-40 Back EMF at 1000 RPM
.
The following parameters have been added for PM motors.
Parameter 1-41 Motor Angle Offset
.
Parameter 1-07 Motor Angle Offset Adjust
.
Parameter 1-14 Damping Gain
.
Parameter 1-47 Torque Calibration
.
Parameter 1-58 Flying Start Test Pulses Current
.
Parameter 1-59 Flying Start Test Pulses Frequency
.
Parameter 1-70 Start Mode
.
Parameter 30-20 High Starting Torque Time [s]
.
Parameter 30-21 High Starting Torque Current [%]
.
N O T I C E
Standard parameters still need configuration (for example
parameter 4-19 Max Output Frequency
).
Table 148: Recommendations for VVC
+
Applications
Application
Settings
Low inertia applications
I
Load
/I
Motor
<5
Increase
parameter 1-17 Voltage Filter Time Const.
by factor 5–10.
Reduce
parameter 1-14 Damping Gain
.
Reduce
parameter 1-66 Min. Current at Low Speed
(<100%).
Low inertia applications
50>I
Load
/I
Motor
>5
Keep calculated values.
High inertia applications
Increase
parameter 1-14 Damping Gain
,
parameter 1-15 Low Speed Filter Time Const.
,
and
parameter 1-16 High Speed Filter Time Const.
AU275636650261en-000101 / 130R0334 | 111
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide