35-45 Term. X48/2 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in
.
35-46 Term. X48/2 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/2. A high time constant
value improves dampening but also
increases the time delay through the filter.
Parameter Descriptions
FC 300 Programming Guide